What additional Information do I need to supply to the cable tray manufacturer for them to best understand and satisfy my needs?
Where? Job site and installation considerations
- Outdoor
- supports available affect the length and strength requirements
- environmental loads, ice, wind, snow, and possibly seismic
- corrosion requirements affect the materials and finishes
- classified hazardous locations affect the cable types acceptable
- Indoor
- support locations available affect the length and strength of the system
- industrial installation may require a 200 lb. Concentrated Load
- commercial or institutional installation may make system appearance, system weight, and space available important factors
- environmental air handling area may affect cable types, cable tray material, or cable tray type and need for covers
- classified hazardous locations affect the cable types acceptable
What?
- Type and number of cables to support
- NEC cable fill requirements dictate size, width and depth, of system
- cable support requirement may control bottom type
- largest bending radius of cable controls fitting radius
- total of cable weight determines load to support
- Future requirements
- cable entry / exit freedom
- design partially full or an expandable system
- support type to allow for needs